Science Inventory

ENVIRONMENTAL TECHNOLOGY VERIFICATION REPORT - ON-SITE SODIUM HYPOCHLORITE GENERATION AND INACTIVATION OF PSEUDOMONAS IN RAW DRINKING WATER, CLORTEC T-12 EXCELTEC INTERNATIONAL CORPORATION, A SUBSIDIARY OF SEVERN TRENT SERVICES, INC.

Citation:

U.S. EPA. ENVIRONMENTAL TECHNOLOGY VERIFICATION REPORT - ON-SITE SODIUM HYPOCHLORITE GENERATION AND INACTIVATION OF PSEUDOMONAS IN RAW DRINKING WATER, CLORTEC T-12 EXCELTEC INTERNATIONAL CORPORATION, A SUBSIDIARY OF SEVERN TRENT SERVICES, INC. NSF 01/21/EPADW395, 2001.

Impact/Purpose:

information

Description:

Verification testing of ExcelTec's on-site hypochlorite generation system ClorTec T-12 system was conducted for 30 days between 3/6-5/4/2000. The system is capable of producing at least one pound of chlorine in the form of sodium hypochlorite solution containing 0.8% +/- 0.1%) chlorine equivalent using 4.11 pounds of salt, 3.5 AC kilowatt hours and 15 gallons of water. In addition, the 0.8% sodium hypochlorite solution that the ClorTec T-12 produces on site produced a 4-log kill of Pseudomonas aeruginosa when dosed to achieve a concentration-time products (CT) of 50 based on actual hydraulic retention time or a CT of 26 based on a T10 value.

URLs/Downloads:

report

Record Details:

Record Type:DOCUMENT( ETV DOCUMENT)
Product Published Date:01/01/2001
Record Last Revised:10/15/2008
OMB Category:Other
Record ID: 119312