Full Record Display for the EPA National Library Catalog

RECORD NUMBER: 223 OF 2058

OLS Field Name OLS Field Data
Main Title Bench-scale high-rate disinfection of combined sewer overflows, with chlorine and chlorine dioxide.
Author Moffa, Peter E. ; Tifft, Jr., Edwin C. ; Richardson, Steven L. ; Smith., James E.
Other Authors
Author Title of a Work
Moffa, Peter E.
CORP Author O'Brien and Gere Engineers, Inc., Syracuse, N.Y.;National Environmental Research Center, Cincinnati, Ohio.;Syracuse Univ., N.Y.
Publisher National Environmental Research Center, Office of Research and Development, U.S. Environmental Protection Agency,
Year Published 1975
Report Number EPA-670/2-75-021; EPA-S-802400; EPA-ROAP-21ASY-124
Stock Number PB-242 296
OCLC Number 01416559
Subjects Combined sewers. ; Sewage--Purification. ; Disinfection and disinfectants. ; Combined sewers. ; Disinfection and disinfectants. ; Sewage--Purification.
Additional Subjects Combined sewers ; Overflows ; Disinfection ; Sewage treatment ; Waste water ; Runoff ; Chlorine ; Chlorine oxides ; Bioassay ; Adenosine phosphates ; Bacteria ; Viruses ; Dosage ; Test methods ; Efficiency ; Purification
Internet Access
Description Access URL
http://nepis.epa.gov/Exe/ZyPDF.cgi?Dockey=9100TPH9.PDF
Holdings
Library Call Number Additional Info Location Last
Modified
Checkout
Status
EJAD  EPA 670/2-75-021 Region 3 Library/Philadelphia, PA 08/30/1996
EJBD ARCHIVE EPA 670-2-75-021 Headquarters Library/Washington,DC 04/04/2011
EJBD  EPA 670-2-75-021 c.1 Headquarters Library/Washington,DC 05/17/2013
EKAM  TD747.B45 Region 4 Library/Atlanta,GA 09/25/1998
ELBD  EPA 670-2-75-021 AWBERC Library/Cincinnati,OH 01/02/1998
NTIS  PB-242 296 Most EPA libraries have a fiche copy filed under the call number shown. Check with individual libraries about paper copy. 01/01/1988
Collation xi, 181 p. illus. 27 cm.
Abstract A bench-scale study of high-rate disinfection of combined sewer overflows with chlorine and chlorine dioxide was performed to aid in the design and operation of full-scale prototype treatment facilities. Four logarithm reduction in three indicator bacteria and several common viruses were obtained with 25 mg/l chlorine or 12 mg/l chlorine dioxide in two-minutes contact time. Sequential addition of disinfectants enhanced the process such that only eight mg/l of chlorine followed in 15 to 30 seconds by two mg/l chlorine dioxide were necessary to obtain similar reductions.
Notes "Project no. S-802400 (11020 HFR); Program element no. 1BB034." Bibliography: p. 131-138.
Place Published Cincinnati, Ohio,
Supplementary Notes Prepared in cooperation with Syracuse Univ., N.Y.
Corporate Au Added Ent United States. Environmental Protection Agency. Office of Research and Development.; United States. National Environmental Research Center (Cincinnati, Ohio)
Title Ser Add Ent Research reporting series. Environmental protection technology ; EPA-670/2-75-021.
PUB Date Free Form 1975
Series Title Untraced Environmental protection technology series, EPA-670/2-75-021
NTIS Prices PC A09/MF A01
BIB Level m
Cataloging Source OCLC/T
OCLC Time Stamp 20110926172004
Language eng
SUDOCS Number EP 1.23/2:670/2-75-021
Origin OCLC
Type MERGE
OCLC Rec Leader 01408cam 2200325I 45020