Main Title |
Radon Mitigation in Schools: HVAC Systems in Schools Tend to Have a Greater Impact on Radon Levels Than HVAC Systems in Homes. |
Author |
Leovic, K. W. ;
Craig, A. B. ;
Saum., D. W. ;
|
CORP Author |
Environmental Protection Agency, Research Triangle Park, NC. Air and Energy Engineering Research Lab. ;Infiltec, Falls Church, VA. |
Publisher |
c1990 |
Year Published |
1990 |
Report Number |
EPA/600/J-90/009; |
Stock Number |
PB90-219718 |
Additional Subjects |
Radon ;
School buildings ;
Environmental engineering ;
Radioactive materials ;
Houses ;
Comparison ;
Air conditioning ;
Heating ;
Ventilation ;
Design criteria ;
Operating ;
Pressure distribution ;
Reprints ;
Indoor air pollution ;
Air pollution sampling ;
Soil gases ;
Stationary sources
|
Holdings |
Library |
Call Number |
Additional Info |
Location |
Last Modified |
Checkout Status |
NTIS |
PB90-219718 |
Some EPA libraries have a fiche copy filed under the call number shown. |
|
07/26/2022 |
|
Collation |
6p |
Abstract |
The first part of the two-part paper discusses radon entry into schools, radon mitigation approaches for schools, and school characteristics (e.g., heating, ventilation, and air-conditioning--HVAC--system design and operating) that influence radon entry and mitigation system design. The second part discusses specific mitigation systems that were installed by the U.S. EPA in four Maryland schools. HVAC systems in schools vary considerably and tend to have a greater impact on pressure differentials--and consequently on radon levels--than do heating and air-conditioning systems in houses. If the HVAC system induces a negative pressure relative to the subslab area, radon can be 'pulled' into the building. If the HVAC system pressurizes the building, it can prevent radon entry as long as the fan is running. However, school HVAC systems are normally set back or turned off on evenings and weekends and, even if the HVAC system pressurizes the school during operation, indoor radon levels may build up during the setback periods. The primary mode of radon entry into a school with significantly elevated radon levels is normally from soil gas that is drawn in by pressure differentials between the soil surrounding the substructure and the building interior. |
Supplementary Notes |
Pub. in American Society of Heating, Refrigeration and Air Conditioning Engineers Jnl., v32 n1 p40, 42, 44, 45, Jan 90. See also PB90-219700. Prepared in cooperation with Infiltec, Falls Church, VA. |
NTIS Title Notes |
Journal article Feb 88-Nov 89. |
Title Annotations |
Reprint: Radon Mitigation in Schools: HVAC Systems in Schools Tend to Have a Greater Impact on Radon Levels Than HVAC Systems in Homes. |
Category Codes |
68F; 68A; 89B |
NTIS Prices |
PC A02/MF A01 |
Primary Description |
600/13 |
Document Type |
NT |
Cataloging Source |
NTIS/MT |
Control Number |
019412501 |
Origin |
NTIS |
Type |
CAT |