Full Record Display for the EPA National Library Catalog

RECORD NUMBER: 16 OF 16

Main Title Trickling filter/solids contact performance with rock filters at high organic loadings /
Author Matasci, Raymond N. ; Clark, D. L. ; Heidman, J. A. ; Parker, D. S. ; Petrik, B.
Other Authors
Author Title of a Work
Matasci, Raymond N.
Clark, David L.
Heidman, James A.
Parker, Denny S.
Petrik, Bruce.
Richards, Darrel.
CORP Author Brown and Caldwell, Pleasant Hill, CA. ;Morro Bay, CA.;Environmental Protection Agency, Cincinnati, OH. Water Engineering Research Lab.
Publisher U.S. Environmental Protection Agency,
Year Published 1986
Report Number EPA/600-J-88-010; EPA-68-03-1818
Stock Number PB88-202445
OCLC Number 27882084
Subjects Trickling filters ; Sewage--Purification--Filtration
Additional Subjects Chemical removal(Water treatment) ; Waste water ; Concentration(Composition) ; Water pollution control
Internet Access
Description Access URL
https://nepis.epa.gov/Exe/ZyPDF.cgi?Dockey=20013254.PDF
Holdings
Library Call Number Additional Info Location Last
Modified
Checkout
Status
EJBD  EPA 600-J-88-010 Headquarters Library/Washington,DC 07/25/2013
ELBD ARCHIVE EPA 600-J-88-010 Received from HQ AWBERC Library/Cincinnati,OH 10/04/2023
ELBD RPS EPA 600-J-88-010 repository copy AWBERC Library/Cincinnati,OH 05/09/2016
NTIS  PB88-202445 Some EPA libraries have a fiche copy filed under the call number shown. 07/26/2022
Collation 20 pages : charts, plan ; 28 cm
Abstract The performance of the trickling filter/solids contact (TF/SC) process at high organic loadings was studied at the Morro Bay-Cayucos treatment plant. The average secondary effluent TSS increased only slightly (from 13 mg/L to 15 mg/L) when the filter BOD5 loading was doubled from 480 g/cu m-day (30 ppd/1000 cu ft) to 960 g/cu m-days (60 ppd/1000 cu ft). The rock trickling filter operated without noticeable odors at the higher loading, although Beggiatoa presence indicated the filter was stressed. When the Morro Bay-Cayucos secondary process operated in the trickling filter mode at the lower filter loading, average secondary effluent TSS was 28 mg/L. Work at the Coeur d'Alene, Idaho, trickling filter plant showed that average secondary effluent TSS decreased from 25 mg/L to 16 mg/L when the old shallow secondary clarifier was replaced with a new flocculator-clarifier.
Notes "Presented at the 59th annual conference of the Water Pollution Control Federation, October 9, 1986, Los Angeles, California." "EPA/600-J-88-010." "1986." Includes bibliographical references. EPA 600-J-88-010 per NSCEP's publication title list.
Place Published Cincinnati, OH
Supplementary Notes Pub. in Jnl. of Water Pollution Control Federation, v60 n1 p68-76 Jan 88. Prepared in cooperation with Morro Bay, CA. Sponsored by Environmental Protection Agency, Cincinnati, OH. Water Engineering Research Lab.
Corporate Au Added Ent United States. Environmental Protection Agency.
PUB Date Free Form 1986
NTIS Prices PC A03/MF A01
BIB Level m
Medium unmediated
Content text
Carrier volume
Cataloging Source OCLC/T
OCLC Time Stamp 20160505125734
Language eng
Origin OCLC
Type CAT
OCLC Rec Leader 01494cam 2200349Ka 45020