Main Title |
Fabric filter system study : third annual report / |
Author |
Ladd, K. L. ;
Chambers, R. L. ;
Plunk, O. C. ;
Kunka, S. L.
|
Other Authors |
|
CORP Author |
Southwestern Public Service Co., Amarillo, TX.;Industrial Environmental Research Lab., Research Triangle Park, NC. |
Publisher |
U.S. Environmental Protection Agency, Industrial Environmental Research Laboratory, |
Year Published |
1984 |
Report Number |
EPA/600-7-84-002; PB84141563 |
Stock Number |
PB84-141563 |
OCLC Number |
318647329 |
Subjects |
Air filters--Testing ;
Flue gases--Purification ;
Filter cloth--Testing
|
Additional Subjects |
Air pollution control equipment ;
Particles ;
Air filters ;
Cost analysis ;
Combustion products ;
Industrial wastes ;
Sulfur dioxide ;
Performance evaluation ;
Operating control ;
Maintenance ;
Texas ;
Fabric filters ;
Coal fired power plants ;
Baghouses ;
Amarillo(Texas)
|
Internet Access |
|
Holdings |
Library |
Call Number |
Additional Info |
Location |
Last Modified |
Checkout Status |
EJBD |
EPA 600-S7-84-002 |
In Binder |
Headquarters Library/Washington,DC |
08/30/2018 |
ELBD ARCHIVE |
EPA 600-S7-84-002 |
In Binder Received from HQ |
AWBERC Library/Cincinnati,OH |
10/04/2023 |
NTIS |
PB84-141563 |
Some EPA libraries have a fiche copy filed under the call number shown. |
|
07/26/2022 |
|
Collation |
2 unnumbered pages ; 28 cm |
Abstract |
The report gives results of the third year of operation (ended October 1, 1980) of a fabric filter installed by Southwestern Public Service Co. on its Harrington Station Unit 2 coal-fired boiler in Amarillo, TX. Results of the emissions testing program demonstrated that the 1971 EPA standard of 1.2 lb SO2/million Btu can be met by burning coal with a sulfur content lower than 0.5 percent. Particulate emissions were less than the 0.03 lb/million Btu standard in all four of the particulate emissions tests. Fabric studies to date show that several fabrics have a potential 3-year baglife. The operation and maintenance cost reported for the third year of study is $434,800, or $1.21/yr/kW. Data analysis continued through the third year. Information on boiler O2 levels, air-to-cloth ratio, temperature, system pressure drop, and boiler load is being logged continuously. |
Notes |
"Project summary." "EPA/600-S7-84-002." "Feb. 1984." |