RECORD NUMBER: 390 OF 457Main Title | Screening of Non-CFC Alternatives for High-Temperature Heat Pumps. | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Author | Kazachki, G. ; Gage, C. L. ; | |||||||||||
CORP Author | Acurex Corp., Research Triangle Park, NC.;Environmental Protection Agency, Research Triangle Park, NC. Air Pollution Prevention and Control Div. | |||||||||||
Publisher | 1997 | |||||||||||
Year Published | 1997 | |||||||||||
Report Number | EPA-68-D4-0005; EPA/600/A-97/103; | |||||||||||
Stock Number | PB98-135197 | |||||||||||
Additional Subjects | Heat pumps ; Environmental chemical substitutes ; Thermodynamic properties ; Comparative evaluations ; Material substitution ; Refrigerants ; Chlorofluorocarbons ; Alternatives ; Screening ; Air pollution abatement ; Ozone depletion ; | |||||||||||
Holdings |
|
|||||||||||
Collation | 12p | |||||||||||
Abstract | Ten pure fluids (R134, R134a, R245cb, R227ea, R236fa, RE134, R236ea, R245fa, R245ca, and R123) and three blends are analyzed as refrigerants for high-temperature heat pumps at three sets of evaporating/condensing temperatures: 7/80 deg C, 20/100 deg C, and 30/120 deg C. Aside from the commonly used thermodynamic analytical criteria, design criteria based on an R410a a scroll air-conditioning and heat-pump compressor are applied: discharge pressure of 3.4 MPa continuous and 4.1 to 4.5 MPa short-time, pressure ratio of 10, and isentropic discharge temperature at 130-145 deg C. The heat cost reflecting the market conditions is used to make the final selection. |