Main Title |
Calorimeter Performance Tests of HFC-245ca and HFC-245fa as CFC-11 Replacements. |
Author |
Kazachki, G. S. ;
Gage, C. L. ;
Bayoglu, E. ;
Hendriks, R. V. ;
|
CORP Author |
Acurex Environmental Corp., Research Triangle Park, NC.;Environmental Protection Agency, Research Triangle Park, NC. Air Pollution Prevention and Control Div. |
Publisher |
1997 |
Year Published |
1997 |
Report Number |
EPA-68-D4-0005; EPA/600/A-97/012; |
Stock Number |
PB97-193791 |
Additional Subjects |
Hydrofluorocarbons ;
Calorimeters ;
Performance tests ;
Environmental chemical substances ;
Refrigerants ;
Halohydrocarbons ;
Compressors ;
Thermodynamic cycles ;
Thermodynamic properties ;
Vapor compression refrigeration cycle ;
Evaporation ;
Alternatives ;
Chillers ;
HFC0245ca ;
HFC0245fa ;
CFC-11
|
Internet Access |
|
Holdings |
Library |
Call Number |
Additional Info |
Location |
Last Modified |
Checkout Status |
NTIS |
PB97-193791 |
Some EPA libraries have a fiche copy filed under the call number shown. |
|
07/26/2022 |
|
Collation |
10p |
Abstract |
The paper gives results of compressor calorimeter tests with hydrofluorocarbon(HFC)-245ca and HFC-245fa as alternatives for the refrigerant chlorofluorocarbon (CFC)-11. Tests were performed in a semi-hermetic compressor at evaporating temperatures from 1 to 13 C and condensing temperatures from 40 to 60 C. In these ranges, the capacities and efficiencies of HFC-245ca were confirmed to be lower than of CFC-11, while both capacities and efficiencies of HFC-245fa were significantly higher. The higher-than-expected efficiencies and capacities for HFC-245fa were a result of the higher compressor efficiencies. |