Main Title Determination of Coronal Oxone Production by High Voltage Power Transmission Lines.
Author Whitmor, Frank C. ; Durfe, Robert L. ;
CORP Author Versar, Inc., Springfield, Va.
Year Published 1973
Report Number EPA-68-02-0553; 650/4-73-003;
Stock Number PB-229 994
Additional Subjects Ozone ; Power transmission lines ; Air pollution ; High voltage ; Electric corona ;
Holdings
Library Call Number Additional Info Location Last
Modified
Checkout
Status
NTIS  PB-229 994 Some EPA libraries have a fiche copy filed under the call number shown. 07/26/2022
Collation 145p
Abstract
A sub-scale simulation of a high-voltage transmission line was constructed and operated in a chamber roughly 1.5 meters long by 0.5 meter in diameter to determine ozone production characteristics. Effects of voltage and corona power, conductor size and surface condition, air temperature, relative humidity, and air flow rate (wind velocity) on ozone yield were determined. Of these, corona power (voltage), relative humidity, and air flow rate exhibited significant effects on ozone yield. Averaged yield values ranged from about 3 gm/kw-hr at high humidity (75-80 percent) to about 7 gm/kw-hr at low humidity (25-30 percent). (Author)