Record Display for the EPA National Library Catalog
RECORD NUMBER: 41 OF 120Main Title | Experience with Chlorine Dioxide at Denver's Reuse Plant. | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Author | Lauer, W. C. ; Lohman, S. R. ; Rogers, S. E. ; | |||||||||||
CORP Author | Denver Water Dept., CO.;Environmental Protection Agency, Cincinnati, OH. Water Engineering Research Lab. | |||||||||||
Year Published | 1986 | |||||||||||
Report Number | EPA/600/J-86/148; | |||||||||||
Stock Number | PB87-115721 | |||||||||||
Additional Subjects | Chlorine oxides ; Water treatment ; Waste water reuse ; Pilot plants ; Effectiveness ; Viricides ; Clarification ; Fluid filtration ; Ion exchanging ; Ammonia ; Monitoring ; Chlorites ; Chlorine ; Design ; Generators ; Performance evaluation ; Colorado ; Reprints ; Denver(Colorado) ; Chlorine dioxide ; Chlorates | |||||||||||
Holdings |
|
|||||||||||
Collation | 12p | |||||||||||
Abstract | Researchers at Denver's reuse demonstration plant found that the effectiveness of chlorine dioxide treatment is critically dependent on the performance of the generator. Because high chlorine dioxide yields can be obtained even when excessive concentrations of undesirable by-products are present, chlorine dioxide yield alone cannot be used as a measure of optimum generation conditions. It is necessary to monitor carefully all of the various chlorine species produced--chlorite, chlorine, and chlorate, as well as chlorine dioxide. |