Emission Factor Details
SCC | 10300601 | ||
Level 1 | External Combustion Boilers | ||
Level 2 | Commercial/Institutional | ||
Level 3 | Natural Gas | ||
Level 4 | > 100 Million Btu/hr | ||
POLLUTANT | Nitrogen oxides (NOx) | NEI NOX | CAS |
Primary Control
CHEMICAL REDUCTION |
|||
Emission Factor | 2.800E2 Lb per Million Cubic Feet Natural Gas Burned | ||
Quality | A Emissions Factors Applicability | ||
References | EPA. March, 1998. Section 1.4, Natural Gas Combustion. In: Compilation of Air Pollutant Emission Factors, Volume 1: Stationary Point and Area Sources, Fifth Edition, AP-42, Supplement D. U.S. Environmental Protection Agency, Office of Air Quality Planning and Standards. Research Triangle Park, North Carolina. | ||
AP 42 Section | Chapter 1 Section 1.4 | ||
Formula | |||
Notes | Expressed as NO2. For large and small wall-fired boilers with SNCR control, apply a 24% reduction to the appropriate NOx emission factor. For tangential-fired boilers with SNCR control apply a 13% reduction to the appropriate NOx emission factor. Pre-NSPS. NSPS=New Source Performance Standard as defined in 40 CFR 60 Subparts D and Db. Post-NSPS units are boilers with greater than 250 MMBtu/hr of heat input that commenced construction modification, or reconstruction after August 17, 1971, and units with heat capacities between 100 and 250 MMBtu/hr that commenced construction modification, or reconstruction after June 19, 1984. | ||
Multiple Factor Info |
2 duplicate factors.
This one is different because... Factor is for a Pre-NSPS boiler. |