Science Inventory

ENVIRONMENTAL TECHNOLOGY VERIFICATION: TEST REPORT OF CONTROL OF BIOAEROSOLS IN HLVAC SYSTEMS: AEOLUS CORPORATION SYNTHETIC MINIPLEAT V-CELL, SMV-M13-2424

Citation:

Research Triangle Institute. ENVIRONMENTAL TECHNOLOGY VERIFICATION: TEST REPORT OF CONTROL OF BIOAEROSOLS IN HLVAC SYSTEMS: AEOLUS CORPORATION SYNTHETIC MINIPLEAT V-CELL, SMV-M13-2424. U.S. Environmental Protection Agency, Washington, DC, EPA/600/R-04/134, 2003.

Description:

The Environmental Technology Verification report discusses the technology and performance of the Synthetic Minipleat V-Cell, SMV-M13-2424 air filter for dust and bioaerosol filtration manufactured by Aeolus Corporation. The pressure drop across the filter was 77 Pa clean and 348 Pa dust loaded. The filtration efficiency when the filter was clean was 69% for Bacillus atrophaeus, 64% for Serratia marcescens, and 73% for bacteriophage MS2. The filtration efficiency when the filter was dust loaded was 99% for Bacillus atrophaeus, 99.5% for Serratia marcescens, and 99% for bacteriophage MS2. The ASHRAE 52.2 dust filtration efficiency was 57% for particles between 0.3 and 1.0 micrometers, 85% for particles between 1.0 and 3.0 micrometers, and 97% for particles between 3.0 and 10 micrometers. The minimum efficiency reporting value was 12 at 0.93 cubic meters per sec.

URLs/Downloads:

10_VR_SMV_M13.PDF  (PDF, NA pp,  1  KB,  about PDF)

Record Details:

Record Type:DOCUMENT( PUBLISHED REPORT/ REPORT)
Product Published Date:11/18/2003
Record Last Revised:12/22/2005
Record ID: 87652