Science Inventory

SAMPLING/ANALYTICAL METHOD EVALUATION FOR ETHYLENE OXIDE EMISSION AND CONTROL UNIT EFFICIENCY DETERMINATIONS

Citation:

Steger, J., W. Gergen, AND J. Margeson. SAMPLING/ANALYTICAL METHOD EVALUATION FOR ETHYLENE OXIDE EMISSION AND CONTROL UNIT EFFICIENCY DETERMINATIONS. U.S. Environmental Protection Agency, Washington, D.C., EPA/600/4-88/017.

Description:

Radian Corporation, assisting the Environmental Monitoring Systems Laboratory, Environmental Protection Agency, Research Triangle Park, North Carolina, performed a field evaluation of a method for sampling and analyzing ethylene oxide (EO) in the vent stream from a sterilization chamber and a dilute acid scrubber. The utility of the sampling method for measuring the efficiency of the control unit was also evaluated. The evaluated sampling and analysis procedure used semi-continuous direct sampling with on-line gas chromatographic analysis. Laboratory studies of the sampling method previous to the field test showed that semi-continuous direct sampling was capable of measuring EO emissions to within 11% of the expected value with a between-trial precision of 5 percent.

Record Details:

Record Type:DOCUMENT( REPORT )
Product Published Date:05/24/2002
Record Last Revised:04/16/2004
Record ID: 34856