| Main Title |
Volumetric leak detection in large underground storage tanks. {microform} / |
| Author |
Starr, James W.;
Wise, R. F.;
Maresca, J. W.
|
| CORP Author |
Vista Research, Inc., Mountain View, CA. ;CDM Federal Programs Corp., Fairfax, VA.;Environmental Protection Agency, Cincinnati, OH. Risk Reduction Engineering Lab. |
| Publisher |
Risk Reduction Engineering Laboratory, Office of Research and Development, U.S. Environmental Protection Agency, |
| Place Published |
Cincinnati, OH : |
| Year Published |
1991 |
| Report Number |
EPA/600/2-91/044A; EPA-68-03-3409 |
| Stock Number |
PB92-114966 |
| OCLC Number |
45796123 |
| Subjects |
Underground storage;
Storage tanks;
Leakage;
Volumetric analysis;
Land pollution abatement;
Performance standards;
Pollution regulations;
Crude oil;
Materials tests;
Standards compliance;
Temperature;
Petroleum products
|
| Subject Added Ent |
Underground storage--Safety measures;
Storage tanks--Safety measures;
Chemicals--Storage--Safety measures
|
| Internet Access |
|
| Holdings |
| Library |
|
Call Number |
Additional Info |
Location |
Date Modified |
| ERBD |
|
PB92-114966 |
|
NERL/ESD-LV Library/Las Vegas,NV |
01/26/2001 |
| NTIS |
|
PB92-114966 |
Most EPA libraries have a fiche copy filed under the call number shown. Check with individual libraries about paper copy. |
NTIS |
01/01/1988 |
|
| Collation |
86 p. : ill. ; 28 cm. |
| Abstract |
A set of experiments was conducted to determine whether volumetric leak detection system presently used to test underground storage tanks (USTs) up to 38,000 L (10,000 gal) in capacity could meet EPA's regulatory standards for tank tightness and automatic tank gauging systems when used to test tanks up to 190,000 L (50,000 gal) in capacity. The experiments, conducted on two partially filled 190,000-L (50,000-gal) USTs at Griffiss Air Force Base in upstate New York during late August 1990, showed that a system's performance in large tanks depends primarily on the accuracy of the temperature compensation, which is inversely proportional to the volume of product in the tank. Errors in temperature compensation that were negligible in tests in small tanks were important in large tanks. The experiments further suggest that a multiple-test strategy is also required. |
| Notes |
"August 1991." "EPA contract no.: 68-03-3409." Includes bibliographical references. Microfiche. |
| Supplementary Notes |
Previously announced as PB91-227942 (reannounced as 2 seperate documents). See also PB92-114974. Portions of this document are not fully legible. Prepared in cooperation with CDM Federal Programs Corp., Fairfax, VA. Sponsored by Environmental Protection Agency, Cincinnati, OH. Risk Reduction Engineering Lab. |
| Author Added Ent |
|
| Corporate Au Added Ent |
Risk Reduction Engineering Laboratory (U.S.) ; Vista Research, Inc. |
| PUB Date Free Form |
1991. |
| NTIS Prices |
PC A05/MF A01 |
| BIB Level |
m |
| OCLC Time Stamp |
20010125174651 |
| Cataloging Source |
OCLC/T |
| Language |
eng |
| Origin |
OCLC |
| Type |
MERGE |
| OCLC Rec Leader |
01318nam 2200325Ka 45020 |